E1

DO (B0 to B7) Common Abnormal Voltage

Fanuc · CNC

¿Qué significa E1 ?

This alarm indicates an abnormal voltage condition detected on the common line for digital outputs B0 through B7. This typically signifies an issue with the power supply providing voltage to this group of outputs, or a fault within the connected wiring or load. When active (bit E1 is '1'), the CNC will either issue a status alarm (for I/O Link i) or set a specific bit in the DI area (for I/O Link) to indicate the abnormal state.

Causas comunes

  • Abnormal voltage detected on the common line for digital outputs (B0 to B7).
  • Short circuit on the common for digital output group B.
  • Wiring issue impacting the common voltage of group B digital outputs.
  • Power supply problem for digital output common (B).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the supply voltage at the terminal connected to the DO (B0-B7) common. Verify this voltage is stable and within the specifications for the digital output module.

  2. 2

    Visually inspect the wiring and connections for the DO (B0-B7) common and its loads for any signs of damage, shorts, or loose terminations.

  3. 3

    If multiple external loads share this common, systematically disconnect them one by one to determine if a specific load or its wiring is causing the voltage abnormality.