Resistor Module Abnormal Discharge (2) (ECM)

Fanuc · Macro B CNC Programming

¿Qué significa H ?

The Energy Charge Module's (ECM) Capacitor Modules are discharged due to a malfunction of the discharge circuit, rather than a commanded discharge. This indicates an uncontrolled or premature release of stored energy, suggesting a more severe failure within the discharge control mechanism or the Resistor Module itself.

Causas comunes

  • Second detected instance of abnormal discharge by the resistor module (ECM).
  • Resistor module (ECM) internal short circuit or open circuit.
  • Inadequate discharge path for the resistor module (ECM).
  • Control logic error for the resistor discharge function.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.

  2. 2

    Inspect the Resistor Module (A06B-6158-H030) and its internal thermostat for proper operation and signs of damage or short circuit.

  3. 3

    Check the control signals from the ECM Control Module (A06B-6158-H010) to the discharge circuit for any erroneous commands causing unintended discharge.

  4. 4

    Verify the integrity of the discharge circuit components for any short circuits or component failures that could cause premature discharge.

  5. 5

    Measure the resistance of the Resistor Module (expected 30 ohm, page 578) to ensure it is within specification.

Ver todos los códigos en este manual (26)