Fanuc · Macro B CNC Programming

¿Qué significa U ?

The potential difference across the Energy Charge Module's (ECM) Capacitor Modules is detected to be more than 300V, indicating an unsafe high voltage condition. This suggests a failure in the charging or discharge control, or a dangerous energy imbalance within the module.

Causas comunes

  • Interruption in the main energy supply to the ECM.
  • Loss of DC bus voltage (e.g., below P24-2 threshold).
  • Power supply unit failure.
  • Circuit breaker tripped or blown fuse in the main power line.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.

  2. 2

    Measure the voltage across the Capacitor Modules (A06B-6158-H020) to confirm it exceeds 300V.

  3. 3

    Inspect the ECM Control Module (A06B-6158-H010) for proper regulation of charging and discharging operations.

  4. 4

    Check the Resistor Module (A06B-6158-H030) and its connections to ensure it can properly dissipate energy when commanded or during an emergency stop.

  5. 5

    Verify the main power supply and connected regenerative units for stable operation and correct voltage levels to prevent overcharging of the capacitor modules.

Ver todos los códigos en este manual (26)
Datos técnicos verificados. Última actualización: March 2026