SRVO-097

Pulse Not Established (Track Encoder)

Fanuc · R-30iB Mate + Mate Plus Robot

¿Qué significa SRVO-097 ?

This alarm (Enc:i) indicates that the absolute position of the Pulsecoder (track encoder) cannot be established. This typically occurs during startup or after a power cycle if the encoder's absolute position data is lost, preventing accurate track positioning. The cause and fix are identical to SRVO-075 for robot axes.

Causas comunes

  • Failure of the track encoder to establish initial pulse count.
  • Encoder not receiving power or ground connection.
  • Mechanical misalignment preventing encoder initialization.
  • Parameter configuration error for encoder setup (e.g., P4-33).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Reset the alarm condition.

  2. 2

    Jog the affected axis (one motor revolution) until the alarm no longer occurs to re-establish the Pulsecoder's absolute position.