Traduciendo...
444 n AXIS: INV. COOLING FAN FAILURE

INVERTER COOLING FAN FAILURE

Fanuc · Series 0i-D/0i Mate-D Maintenance

¿Qué significa 444 n AXIS: INV. COOLING FAN FAILURE ?

This warning signal on the Fanuc Series 0i-D/0i Mate-D αi servo system indicates a failure of the inverter cooling fan. This condition will lead to an inverter overheat alarm if not addressed, as reported by the servo amplifier (SVWRN4 active).

Causas comunes

  • Cooling fan motor failure in the inverter unit.
  • Obstruction or blockage of the fan's intake or exhaust preventing proper airflow.
  • Loose or damaged electrical connection to the inverter cooling fan.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Visually inspect the inverter cooling fan for any blockages (e.g., dust, debris) or physical damage to the fan blades.

  2. 2

    Check the electrical connection to the fan motor for proper seating and continuity.

  3. 3

    Attempt to manually spin the fan blades (with power off) to check for binding or excessive resistance.

  4. 4

    Verify the fan's operation by observing rotation during system power-on (if safe to do so).

  5. 5

    If the fan is confirmed to be faulty or non-operational, replace the inverter cooling fan unit.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Fanuc Series 0i-D/0i Mate-D Maintenance