Inverter: IPM alarm (L axis) or Overheat
Fanuc · Series 30i/31i/32i-MODEL B Plus
¿Qué significa 8. ?
An Intelligent Power Module (IPM) alarm has occurred for the L axis. This can indicate a short-circuit or ground fault in the power lead phases or motor winding phases, or an internal IPM failure. Additionally, it may signal an IPM overheat condition, often caused by the motor operating under harsh conditions or excessively high ambient temperatures. This fault implies a critical power module issue.
Causas comunes
- Short-circuit between power lead phases or ground fault in them
- Short-circuit between motor winding phases or ground fault in them
- The motor is being used under a harsh condition
- The ambient temperature is high
- Servo Amplifier failure
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure insulation resistance of power lead phases to ground using a megohmmeter.
- 2
Measure insulation resistance between motor winding phases and from each phase to ground.
- 3
Assess the motor's operating conditions and load to ensure they are within specifications.
- 4
Measure the ambient temperature around the inverter and confirm it is within specified environmental limits.
- 5
If external electrical and environmental checks are good, replace the Servo Amplifier.