309

DC input voltage MPPT 1 too high

Fronius · Primo GEN24 Operating Instructions

¿Qué significa 309 ?

This code indicates that the DC input voltage from the PV string connected to Maximum Power Point Tracker 1 (MPPT 1) is too high. This triggers a short-term interruption in energy feeding, and the inverter will attempt to resume its startup routine.

Causas comunes

  • PV string connected to MPPT1 has an open-circuit voltage (Voc) that exceeds the inverter's maximum input voltage.
  • Faulty PV modules in the string leading to excessive voltage.
  • Incorrect string configuration or number of modules for MPPT1.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    If the status code is displayed continuously, notify a Fronius-trained service engineer.

  2. 2

    Verify the open-circuit voltage (Voc) of the PV string connected to MPPT1 and ensure it is within the inverter's specified limits.

  3. 3

    Reconfigure or modify the PV string connected to MPPT1 if its voltage exceeds the inverter's rating.

Ver todos los códigos en este manual (60)