Traduciendo...
303

Insulation fault on PV generator

Fronius · Primo GEN24

¿Qué significa 303 ?

The Fronius Primo GEN24 208-240 inverter has detected a general insulation fault (ground fault) on the entire PV generator. This implies an unintended electrical path between the PV array's DC conductors and ground, which can be a safety risk and prevents inverter operation.

Causas comunes

  • Insulation fault on PV generator.
  • Water ingress into PV modules or junction boxes.
  • Damaged PV cable insulation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Safely disconnect all PV arrays from the Fronius Primo GEN24 208-240 inverter using the DC disconnector and AC breaker.

  2. 2

    Measure the insulation resistance of each PV string (PV1, PV2, etc.) to ground using a megohmmeter - expect >1 MΩ.

  3. 3

    Conduct a thorough visual inspection of all PV modules, cables, and connectors in the entire PV system for signs of damage, moisture ingress, or degradation.

  4. 4

    Systematically check all junction boxes, combiner boxes, and cable conduits for moisture, corrosion, or loose connections.

  5. 5

    Isolate PV strings or modules one by one and retest to identify the specific faulty component.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas