505

Overvoltage on DC side (PV1)

Fronius · Primo GEN24

¿Qué significa 505 ?

The Fronius Primo GEN24 208-240 inverter has detected an excessively high voltage from the PV1 string on the DC side, exceeding its maximum input voltage rating. This can lead to inverter damage.

Causas comunes

  • Overvoltage on the DC side (PV1).
  • Incorrect PV array sizing (too many modules in series).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the PV1 string using the DC disconnector and measure the open-circuit voltage (Voc) of the PV1 string.

  2. 2

    Compare the measured Voc with the maximum DC input voltage specification of the Fronius Primo GEN24 208-240 inverter.

  3. 3

    Verify the number of PV modules in series for PV1; ensure it does not exceed the inverter's maximum voltage rating, considering temperature effects (lower temperatures lead to higher Voc).

  4. 4

    Check for any miswiring or faulty components in the PV1 string that could cause abnormal voltage readings.

  5. 5

    If the array configuration is correct and voltage is within limits, restart the inverter to clear the temporary fault. If it reoccurs, contact Fronius service.