Traduciendo...
105

AC frequency too high

Fronius · Symo Advanced Manual

¿Qué significa 105 ?

The grid frequency is above the permissible range, and the inverter cannot feed energy into the grid due to compliance standards. This indicates a grid condition, not an inverter fault.

Causas comunes

  • Public grid frequency instability, exceeding upper limits

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure AC grid frequency at the inverter's main input terminals using a calibrated power quality meter to independently verify grid conditions.

  2. 2

    Verify the inverter's configured grid code and frequency monitoring parameters (e.g., Fmax, F_Stop, trip thresholds) in the system settings, ensuring they comply with local utility requirements.

  3. 3

    Inspect all AC input wiring and connections to the inverter for proper termination, torque, and absence of damage or corrosion, ensuring reliable measurement and operation.

  4. 4

    Monitor the AC grid frequency over an extended period and observe if other grid-tied devices or sensitive equipment in the area are experiencing similar frequency-related disturbances.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas