2001

High string input voltage

Huawei · SUN2000-(3KTL-10KTL)-M1 Solar Inverter

¿Qué significa 2001 ?

The PV array is not properly configured, with too many PV modules connected in series, causing the PV string open-circuit voltage to exceed the maximum SUN2000 operating voltage. This can damage the inverter.

Causas comunes

  • Excessive PV modules are connected in series to the PV string; therefore the PV string open-circuit voltage exceeds the maximum SUN2000 operating voltage.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Reduce the number of PV modules connected in series to the PV string until the PV string open-circuit voltage is less than or equal to the maximum SUN2000 operating voltage.

Ver todos los códigos en este manual (24)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Huawei SUN2000-(3KTL-10KTL)-M1 Solar Inverter