Traduciendo...
326
Electrical Grounding Fault
Huawei · SUN2000 8-28KTL Solar Inverter
¿Qué significa 326 ?
A major fault indicating that the neutral wire or PGND cable is not connected to the SUN2000, or an isolation transformer is missing at the output side when PV strings are grounded. This prevents proper electrical grounding of the inverter, posing a safety risk and operational instability.
Causas comunes
- The neutral wire or PGND cable is not connected to the SUN2000.
- An isolation transformer is not connected to the SUN2000 at the output side when the PV strings are grounded.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify that the neutral wire and PGND cable are properly connected to the SUN2000.
- 2
Confirm that an isolation transformer is connected to the SUN2000 at the output side if the PV strings are grounded.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Huawei SUN2000 8-28KTL Solar Inverter