String Voltage High

String Voltage High

Huawei · SUN2000 Series Solar Inverter

¿Qué significa String Voltage High ?

This alarm indicates that the DC SWITCH has automatically turned off because the voltage of one or more PV strings has exceeded the maximum allowable input voltage for the SUN2000 inverter. Sustained overvoltage can lead to critical component failure, permanent damage to the inverter, and safety hazards.

Causas comunes

  • PV string voltage exceeding the inverter's maximum input voltage due to incorrect string sizing (too many modules in series).
  • Open-circuit voltage of PV modules increasing under low temperature conditions, surpassing the design limits.
  • Incorrect PV module selection for the SUN2000 inverter model.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Identify and rectify the cause of the high string voltage, such as checking PV module configurations.

  2. 2

    After rectification, wait for at least 3 minutes.

  3. 3

    Set the DC SWITCH handle to OFF to complete the reset procedure.

  4. 4

    Set the DC SWITCH handle to ON to restart the inverter.

Ver todos los códigos en este manual (4)