Motor Overtemperature Shutdown
Indramat · ECODRIVE Controller
¿Qué significa F219 ?
The motor temperature has risen to an unacceptable level. As soon as the temperature error threshold (155°C) is exceeded, the drive will immediately bring the motor to a standstill as set in parameter P-0-0119 (best possible standstill).
Causas comunes
- The motor was overloaded; the effective torque demanded was above its allowable continuous torque level for too long.
- Break in line, ground short, or short circuit in the motor temperature monitor line.
- Instability in the velocity loop.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the installation and loading of the motor. Verify if operating conditions have changed (e.g., pollution, friction, moved components).
- 2
Check wires and cables to the motor temperature monitor for wire breaks, earth short circuits, or short circuits.
- 3
Review and adjust the velocity loop parameters in the ECODRIVE DKC01.1/DKC11.1 controller for stability.