Digital Output Overcurrent/Short Circuit
Indramat · ECODRIVE Controller
¿Qué significa F262 ?
This fault indicates that a digital output on the drive controller has exceeded its permissible current limit or experienced a short circuit. The drive triggers a shutdown to protect the output circuitry from damage. The specific current limit may vary depending on the output channel, with some outputs having a limit of 350mA and others 80mA.
Causas comunes
- A short circuit present on one of the digital outputs.
- The load connected to a digital output draws excessive current, exceeding its specified limit (e.g., > 350mA or > 80mA).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Identify the specific digital output causing the fault.
- 2
Disconnect the load from the affected digital output and measure the current draw of the load separately, ensuring it is within the specified limits (<350mA or <80mA).
- 3
Check the wiring connected to the digital output for any short circuits to ground or to other potentials using a multimeter.
- 4
Replace the faulty load device if it is drawing excessive current or has an internal short circuit.