Traduciendo...
E2270

Analog input 1 or 2, wire break

Indramat · IndraDrive MPx02

¿Qué significa E2270 ?

The IndraDrive MPx02 has detected an open circuit or wire break on either analog input 1 or analog input 2. This means the drive is not receiving a valid signal from the connected analog sensor or command source, potentially leading to incorrect control, erratic behavior, or machine safety issues.

Causas comunes

  • Disconnected wire at the analog input terminal (e.g., X31 for AI1, X32 for AI2) on the drive or at the sensor/signal source.
  • Broken or damaged cable between the sensor/signal source and the IndraDrive MPx02.
  • Faulty sensor or signal generator providing the analog signal.
  • Incorrect wiring (e.g., common connection missing, wrong polarity) preventing signal reception.
  • Short circuit protection or an internal drive input circuit fault.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Immediately power down the drive and visually inspect the wiring connections at the analog input terminals (e.g., X31 for Analog Input 1, X32 for Analog Input 2) on the IndraDrive MPx02.

  2. 2

    Check the entire length of the cable from the analog sensor or signal source to the drive for any physical damage or breaks.

  3. 3

    Measure the voltage or current signal directly at the sensor output and then again at the drive's input terminals to identify where the signal is lost.

  4. 4

    Verify that the sensor is correctly powered and functioning, and check its output range matches the drive's configured analog input range.

  5. 5

    Ensure correct polarity and common connections are made. If the wiring is correct and the sensor is verified, the issue might be an internal drive input circuit fault, requiring service.

Ver todos los códigos en este manual (56)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Indramat E2270 soporte: Analog input 1 or 2, wire break aná… | ErrorLib