HW control of braking resistor
Indramat · IndraDrive MPx02
¿Qué significa E2802 ?
This warning indicates an issue related to the hardware control of the external braking resistor connected to the IndraDrive MPx02. This could imply a fault in the braking resistor circuit, the drive's internal brake chopper, or its control, preventing effective dissipation of regenerative energy.
Causas comunes
- Overload or overheating of the braking resistor, causing its thermal protection to trip.
- Short circuit or open circuit in the braking resistor wiring.
- Internal fault of the drive's brake chopper circuit.
- Incorrect sizing or parameterization of the braking resistor in the drive configuration.
- Failure of the thermal switch on the resistor (if equipped) to provide accurate feedback.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the braking resistor and its wiring for any signs of damage, loose connections, or overheating. Allow it to cool if hot.
- 2
Measure the resistance of the braking resistor to confirm it matches the specified value and is not open-circuited or short-circuited.
- 3
Check if the braking resistor has an integrated thermal switch and verify its continuity; if open, the resistor is likely overheated.
- 4
Verify that the braking resistor's power rating and resistance are correctly configured in the IndraDrive MPx02 parameters (e.g., P-0-0115, Braking resistor continuous power).
- 5
If the resistor and wiring are confirmed good, but the error persists, the issue might lie with the drive's internal brake chopper circuit. Contact Indramat service.