F4001

Double MST failure shutdown

Indramat · Indradrive

¿Qué significa F4001 ?

The drive detected a simultaneous failure of two Master Status Telegrams (MST). This is a critical communication error indicating a severe disruption in the primary communication link between the master controller and the IndraDrive, leading to a shutdown to ensure safety.

Causas comunes

  • Complete loss of communication signal on the bus (e.g., PROFIBUS, SERCOS, EtherCAT).
  • Faulty communication cable or connectors.
  • Problem with the master controller's communication interface.
  • Severe electromagnetic interference disrupting bus communication.
  • Defective communication interface on the IndraDrive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the communication cable (e.g., fiber optic, copper) connecting the IndraDrive to the master controller for damage or loose connections.

  2. 2

    Verify the status of the master controller's communication interface and bus activity.

  3. 3

    Check for external sources of electromagnetic interference that might affect the communication bus.

  4. 4

    Power cycle the IndraDrive and the master controller.

  5. 5

    If possible, swap the communication cable with a known good one or try connecting to a different port on the master.