Axis 1 Not Homed
Indramat · ServoDyn D Servo Drive
¿Qué significa 05 ?
This error indicates that Axis 1 of the CLM01.3-M has not completed its homing procedure, which is a mandatory step before operating in Automatic mode. The system cannot perform absolute positioning without a defined home reference.
Causas comunes
- Attempting to select Automatic mode for Axis 1 before a successful homing cycle has been performed.
- Homing procedure for Axis 1 was initiated but not completed successfully due to an interruption or fault.
- Incorrect configuration of homing parameters (Parameter 08, Homing Setup and Parameter 09, Homing Offset) for Axis 1.
- Faulty home limit switch or wiring preventing Axis 1 from detecting its home position.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Switch the CLM01.3-M to Manual mode.
- 2
Perform the homing procedure for Axis 1 as described in the manual to establish a home reference.
- 3
Verify that Parameter 08 (Homing Setup) and Parameter 09 (Homing Offset) for Axis 1 are correctly configured per the application's requirements (refer to Chapter 4).
- 4
Inspect the home limit switch for Axis 1, including its wiring and mechanical actuation, to ensure it is functioning correctly.
- 5
Check for any mechanical obstructions or binding that might prevent Axis 1 from reaching its home position during the homing cycle.