This error occurs if the absolute encoder for Axis 2 is not properly connected, or if data transmission between the encoder and the CLM01.3-M is interrupted or corrupted. This prevents the system from obtaining an absolute position reference for Axis 2.

Causas comunes

  • Absolute encoder cable for Axis 2 is disconnected, damaged, or incorrectly wired (to CLM01.3-M connector X2).
  • Data transmission error from the absolute encoder to the CLM01.3-M.
  • Defective Axis 2 absolute encoder.
  • Incorrect Encoder Data A2 parameter (P41) setting for the type of absolute encoder used.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that Parameter P41 (Encoder Data A2) for Axis 2 correctly matches the specifications of the installed absolute encoder.

  2. 2

    Inspect the physical connections of the absolute encoder cable to both the Axis 2 motor and CLM01.3-M connector X2 for secure and correct wiring.

  3. 3

    Check the absolute encoder cable for any signs of damage, fraying, or loose shielding.

  4. 4

    Test the absolute encoder for proper operation, potentially by checking its output signals if diagnostic tools are available.

  5. 5

    If the error persists after thorough checks, consider replacing the absolute encoder or its cable.