35

Max Travel Lmt 2

Indramat · ServoDyn D Servo Drive

¿Qué significa 35 ?

This error occurs in Automatic mode for Axis 2 if the commanded position is greater than the value configured in Parameter 52 (Maximum Travel Limit A2). The system detects an attempt to move Axis 2 beyond its defined maximum operational boundary.

Causas comunes

  • The programmed command attempts to move Axis 2 above its Maximum Travel Limit set in Parameter 52.
  • Parameter 52 (Maximum Travel Limit A2) is set incorrectly or too low for the actual mechanical limits of Axis 2.
  • Overshoot of Axis 2 during acceleration or homing, causing it to briefly exceed the maximum limit.
  • Incorrect position gain (Parameter 45) or tuning, leading to poor positioning accuracy for Axis 2.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    The Axis 2 commanded position has exceeded the Axis 2 maximum travel limit.

  2. 2

    Ensure that Parameter 52 (Maximum Travel Limit A2) is correctly set to reflect the actual maximum mechanical travel limit for Axis 2.

  3. 3

    Adjust the user program to ensure that commanded positions for Axis 2 do not exceed the value specified in Parameter 52.

  4. 4

    Optimize the position gain (Parameter 45) for Axis 2 to improve acceleration and stopping accuracy if overshoot is observed.

  5. 5

    Inspect the mechanical system for any binding or obstructions that could restrict movement or cause overtravel for Axis 2.

Ver todos los códigos en este manual (51)
Datos técnicos verificados. Última actualización: March 2026