Traduciendo...
RS 08

RS Stat # Wrong

Indramat · ServoDyn D Servo Drive

¿Qué significa RS 08 ?

This serial communication error indicates that an incorrect format was used to request status information from the CLM01.3-M. This could be due to an invalid status number or a general formatting issue with the status request command string.

Causas comunes

  • The status number requested in the serial command is invalid or not recognized by the CLM01.3-M.
  • The overall format of the status request command string (e.g., prefix, station number, CR/LF) is incorrect.
  • Corrupted data during serial transmission, leading to a misinterpretation of the status request.
  • Sending device software bug, generating malformed status requests.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify that the status number and the entire status request command string are transmitted in the correct format. Refer to Chapter 7 (Serial Interface).

  2. 2

    Check the requested status number against the list of valid status numbers for the CLM01.3-M in Chapter 7 (e.g., Status 00-81).

  3. 3

    Ensure the serial communication settings (baud rate, parity, word length, stop bits) on both devices are identical.

  4. 4

    Re-transmit the status request command after correcting any formatting issues.

  5. 5

    Use a serial terminal program to verify the exact string being sent to the CLM01.3-M for debugging.

Ver todos los códigos en este manual (51)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Indramat ServoDyn D Servo Drive