Traduciendo...
1031

VMN HIGH

Kone · Elevator Control

¿Qué significa 1031 ?

The motor controller (codes 1031, 2031, 3031) has detected that its VMN (motor voltage) is too high. This indicates an overvoltage condition for the motor. The specific lift reaction is controller dependent.

Causas comunes

  • Overvoltage condition on the battery supply.
  • Issue with regenerative braking causing voltage spikes.
  • Internal power supply fault within the motor controller.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure incoming AC supply voltage at the drive's input terminals to verify it is within the specified tolerance.

  2. 2

    Verify the DC-link voltage displayed on the drive's HMI or diagnostic tool is within the nominal operating range.

  3. 3

    Inspect the braking resistor and its associated wiring for physical damage, proper connection, and verify its resistance value if applicable.

  4. 4

    Verify all motor controller parameters related to voltage limits, acceleration/deceleration ramps, and braking resistor configuration are correctly set according to elevator specifications.

  5. 5

    Inspect motor power cables for any signs of damage, insulation breakdown, or loose connections.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas