59 Parallel Coil Fault
Kone · Elevator Control
¿Qué significa 59 ?
A fault has been detected in the parallel coil, indicating an electrical issue with this specific solenoid. This disables both lifting and driving functions.
Causas comunes
- Parallel coil open circuit, short circuit, or high resistance.
- Damaged wiring or loose connections to the parallel coil.
- Control circuit failure attempting to activate the coil.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the identification and physical location of the 'parallel coil' solenoid within the Kone Kone Elevator Control system schematics.
- 2
Inspect all associated wiring, connectors, and terminals of the parallel coil solenoid for damage, loose connections, or corrosion.
- 3
De-energize the system. Measure the resistance of the parallel coil solenoid across its terminals and compare the reading to the nominal value specified in the electrical documentation.
- 4
Energize the system. Measure the supply voltage at the parallel coil solenoid terminals when commanded to activate, ensuring it matches the specified operating voltage.