Drive stop
Kone · V3F25/18 drive
¿Qué significa 0101 ?
Emergency stop or error detected by the V3F25/18 drive diagnostics. This is a general fault indicating that a specific fault code should be present to determine the root cause.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the Kone V3F25/18 drive's display or diagnostic log for any specific fault codes or detailed messages beyond the general 0101.
- 2
Verify the status of all connected emergency stop buttons, safety relays, and safety interlocks in the control circuit, ensuring they are closed and reset.
- 3
Verify the drive's enable and run command signals are present and stable at the control input terminals, using the drive's diagnostic I/O status screen.
- 4
Measure the incoming three-phase supply voltage at the drive's L1, L2, L3 input terminals and compare against the specified nominal voltage.