Traduciendo...
141
BR1-Trip (Brake error, main axes)
Kuka · KR C2 Robot Controller
¿Qué significa 141 ?
This fault indicates an error in the brake system for the main axes (KPS-600). This could be due to a faulty brake component, incorrect brake control signals, or issues with the brake power supply, potentially compromising safety and the ability to hold the main axes.
Causas comunes
- BR1-Trip: Brake error detected on main axes (P1-22).
- Mechanical brake failure on the primary axes.
- Incorrect wiring or faulty connection to the main brake.
- Control signal error for the main brake engagement.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the brake control signal voltage at the brake terminals during activation and deactivation cycles.
- 2
Measure the resistance of the brake coil for the main axes and compare it to specifications.
- 3
Inspect the brake wiring and connectors for continuity and secure connection.
- 4
Check for mechanical obstruction preventing brake release or engagement.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Kuka KR C2 Robot Controller