CAN-IN1 Sync Communication Error
Lenze · 8200 Series
¿Qué significa ce1 ?
A communication error has occurred on CAN-IN1 during synchronous control, indicating that faulty data is being received or the communication itself is interrupted. This can be caused by loose bus module connections or issues with the transmitting device. Loss of synchronous communication can lead to unsynchronized operation or system shutdown.
Causas comunes
- Loose or improperly seated CAN-IN1 bus module or connector on the drive controller.
- Break or short circuit in the CAN-IN1 bus cabling, particularly within a synchronous network.
- Incorrect CAN bus termination resistors (120 Ohm) are missing or improperly installed at the network ends.
- Excessive electrical noise on the CAN-IN1 bus affecting signal integrity during synchronous data exchange.
- Communication parameters (e.g., baud rate, node ID) in P8-01 (CAN-IN1 baud rate) or P8-02 (CAN-IN1 node ID) do not match other synchronous devices.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the CAN-IN1 communication module is securely seated in its slot on the drive controller.
- 2
Inspect the CAN-IN1 bus cable for physical damage, especially at connectors and strain relief points.
- 3
Measure the resistance across the CAN_H and CAN_L lines at the network's physical ends; it should be approximately 60 Ohms (two 120 Ohm terminators in parallel).
- 4
Confirm CAN-IN1 communication parameters, including baud rate (P8-01) and node ID (P8-02), are correctly set for all devices in the synchronous network.
- 5
Check for proper shielding and grounding of the CAN-IN1 bus cable, ensuring it is separated from high-voltage power cables.