Traduciendo...
0107

H07 (Internal fault (power stage))

Lenze · 9300 Series

¿Qué significa 0107 ?

During the controller's initialization phase, an incorrect power stage was detected. This implies a critical internal hardware mismatch or failure within the power electronics.

Causas comunes

  • Incorrect or incompatible power module installed in a modular drive system.
  • Failure of internal power stage components (e.g., IGBTs, rectifiers) detected during self-test.
  • Disconnection or poor contact between the control board and the power board.
  • Internal sensor fault on the power stage (e.g., current sensor, voltage sensor) preventing correct identification.
  • Manufacturing defect or significant physical damage to the power stage assembly.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Perform a complete power cycle to the drive by disconnecting mains power for at least 60 seconds to allow all internal capacitors to discharge.

  2. 2

    If the drive is modular, physically inspect the power module for proper seating and connection to the control unit.

  3. 3

    Verify the drive's model number and series to ensure the correct power module (if replaceable) is installed for the control unit.

  4. 4

    Visually inspect the power stage for signs of damage, such as burnt components, bulging capacitors, or discolored PCBs.

  5. 5

    Measure the resistance of the motor phases (U, V, W) to ground and between phases with a megohmmeter (e.g., 500VDC) to rule out motor or cable insulation breakdown affecting power stage.

Ver todos los códigos en este manual (145)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas