Traduciendo...
079

PI

Lenze · 9300 Series

¿Qué significa 079 ?

A fault occurred during parameter initialization, likely during parameter set transfer between two devices, or because the parameter set does not match the controller (e.g., from a higher-power controller to a lower-power one).

Causas comunes

  • Incompatibility between the loaded parameter set and the specific drive hardware or firmware version.
  • Attempting to load a parameter set from a higher power rated drive into a lower rated drive, or vice versa, leading to range errors.
  • Incomplete or interrupted parameter transfer due to communication error or premature power cycle.
  • Internal non-volatile memory (EEPROM) write error within the drive during parameter storage.
  • Incorrect selection of the parameter set to be activated (e.g., attempting to activate a non-existent set).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Perform a factory reset (e.g., Parameter C0004 = 1) to clear existing parameters, then restart the drive.

  2. 2

    2. Ensure the correct parameter set, matching the drive's model and firmware revision, is used for upload.

  3. 3

    3. Re-attempt the parameter transfer from a verified, compatible source using a stable communication link.

  4. 4

    4. Manually configure essential parameters (e.g., motor data, min/max frequency) via the keypad and save them to a new parameter set.

  5. 5

    5. Verify that no parameters are being written with values outside their permissible range during the transfer.

Ver todos los códigos en este manual (145)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas