087

Sd7

Lenze · 9300 Series

¿Qué significa 087 ?

An initialization error occurred at the absolute value encoder at X8, or the encoder electronics are defective. This can result from a loose cable, an open circuit, an incorrect encoder type, or failure during rotor position adjustment.

Causas comunes

  • Encoder cable disconnection: Loose connection at encoder connector (e.g., X8) or at the encoder side, causing complete signal loss.
  • Open circuit in cable: One or more conductors (e.g., power, ground, data lines) in the absolute encoder cable are broken, preventing communication.
  • Incorrect encoder type: An unsupported or incompatible absolute encoder type is connected to terminal X8, or the encoder selection parameter (e.g., P4-10) is set incorrectly.
  • Encoder power supply issue: The encoder's internal electronics are not receiving sufficient voltage (e.g., 5V or 24V supply via X8/1 and X8/2) due to a short or fault.
  • Defective encoder hardware: The absolute encoder itself has an internal electronic failure and is not transmitting valid initialization data.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify all connections at terminal X8 on the device and at the absolute encoder connector, ensuring they are tight and properly seated (e.g., visual inspection for loose pins).

  2. 2

    Using a multimeter, measure the resistance and continuity of each conductor in the encoder cable from X8 to the encoder, paying attention to power (e.g., +5V/24V) and data lines.

  3. 3

    Measure the supply voltage delivered to the encoder via X8 (e.g., +5V or +24V between pins X8/1 and X8/2) to ensure it is stable and within specification.

  4. 4

    Check the encoder type selection parameter (e.g., P4-10 or encoder initialization parameters) to ensure it matches the connected absolute encoder model.

  5. 5

    If possible, swap the suspected absolute encoder with a known-good encoder of the same type to isolate whether the fault is with the encoder or the drive's input.

Ver todos los códigos en este manual (145)