OC6

I²xt overload

Lenze · 9300 Series

¿Qué significa OC6 ?

This fault signifies a cumulative thermal overload condition based on the square of current and time, resulting from frequent and prolonged acceleration processes with motor overcurrent or permanent motor overload with Imotor > Irmotor. This can severely stress the motor and drive components.

Causas comunes

  • Continuous motor operation above its rated current (e.g., Imotor > 1.05 x C0203) for extended periods, leading to thermal buildup.
  • Frequent and heavy acceleration/deceleration cycles that repeatedly push the motor current significantly above its nominal value.
  • Motor cooling fan failure or obstructed ventilation preventing adequate heat dissipation from the motor windings.
  • High ambient temperature (e.g., >40°C) surrounding the motor and drive, reducing their effective thermal capacity.
  • Incorrect motor thermal model parameters in the drive (e.g., C0203, P1-54, P1-55) not accurately reflecting the motor's characteristics.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Monitor the motor current (C0004) and motor temperature (C0005, if sensor connected) during operation to identify sustained overload conditions.

  2. 2

    Reduce the mechanical load on the motor if possible, or consider upsizing the motor to match the application requirements.

  3. 3

    Increase acceleration and deceleration ramp times (e.g., C0256, C0257) to lower peak currents during dynamic operations.

  4. 4

    Inspect the motor's cooling fan for proper operation and ensure that air vents on both the motor and drive are clear of obstructions.

  5. 5

    Verify that the motor rated current (C0203) is correctly entered into the drive and that any service factor settings (P1-54, P1-55) are appropriate for the motor.

Ver todos los códigos en este manual (145)