OH7

Motor overtemperature (C0121)

Lenze · 9300 Series

¿Qué significa OH7 ?

The motor temperature, detected via resolver or incremental encoder, has exceeded the threshold set in C0121. This indicates thermal overload from impermissible continuous current, frequent/prolonged acceleration processes, or the C0121 value being set too low.

Causas comunes

  • Motor temperature sensor reading (C0121) indicates overtemperature, requiring immediate shutdown.
  • Motor is operating beyond its rated capacity, causing excessive heat buildup.
  • Faulty motor temperature sensor reporting an incorrect high value.
  • Inadequate motor cooling or ventilation.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check drive dimensioning to prevent continuous motor overload.

  2. 2

    Correct wiring if no PTC/temperature contact is connected for reliable temperature sensing.

  3. 3

    Enter a higher value in C0121 if the temperature threshold is set too low.

  4. 4

    Switch off monitoring by setting C0584 = 3.