Resolver error at X7
Lenze · 9300 Series
¿Qué significa Sd2 ?
The resolver cable connected to X7 is interrupted, or the resolver itself is faulty. This prevents accurate motor position feedback, which is crucial for precise motor control.
Causas comunes
- Open circuit or high resistance in the resolver excitation winding cable (e.g., X7/1 to X7/2), preventing excitation signal.
- Open circuit or short circuit in the resolver sine/cosine feedback windings cable (e.g., X7/3 to X7/4, X7/5 to X7/6), leading to no position signal.
- Damaged resolver sensor within the motor itself, often due to mechanical shock, overheating, or ingress of contaminants.
- Incorrect shielding or grounding of the resolver cable, leading to noise interference on the low-level sine/cosine signals.
- Loose or corroded connections at the X7 terminal block on the controller or at the resolver motor connector.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Power off the drive, disconnect the resolver cable from X7, and measure resistance across X7/1-X7/2 (excitation) and X7/3-X7/4, X7/5-X7/6 (feedback) for open circuits.
- 2
Using a multimeter, check for continuity of each individual wire in the resolver cable from end to end (connector to X7 terminals).
- 3
Inspect the resolver cable for cuts, kinks, or signs of crushing; replace the cable if physical damage is evident.
- 4
Verify the integrity of the cable shield connection at both the motor and the X7 connector on the controller.
- 5
With power on, use an oscilloscope to check for the presence and amplitude of the excitation signal on X7/1 and X7/2 terminals (typically 5-10V AC).
- 6
If possible, swap the resolver with a known good one (if available) to confirm if the resolver sensor or the drive input is at fault.