EPM data: unknown parameter found
Lenze · i550 Protec Drive
¿Qué significa 0x7696 ?
The memory module (EPM) contains parameter settings that are not recognized by the current inverter software. This can happen after firmware updates or compatibility changes.
Causas comunes
- Firmware version of the inverter is older than the firmware version used to save parameters to the EPM, resulting in unrecognized new parameters.
- A firmware update on the inverter changed or removed certain parameters, and the EPM still holds values for these outdated parameters.
- The EPM module was used with a different drive model or series that has a distinct parameter set, leading to foreign parameter entries.
- Data corruption on the EPM module, causing invalid parameter addresses or values to be stored.
- Improper parameter saving process, potentially leading to incomplete or corrupted data on the EPM.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Connect to the inverter with the configuration software and upload parameters from the EPM to identify the 'unknown' parameters if possible.
- 2
Update the inverter's firmware to the latest available version. Then perform a parameter initialization (e.g., P99.00 = 1) and reconfigure parameters.
- 3
If a known good and compatible EPM is available, try swapping it to see if the fault clears.
- 4
Perform a factory reset of the inverter (e.g., P99.00 = 1) to ensure all parameters are at default values, then re-enter application-specific settings.
- 5
Manually review and compare the parameter list from the EPM (if readable) with the current inverter's parameter manual to pinpoint discrepancies.