Network: user fault 1
Lenze · i550 Protec Drive
¿Qué significa 25249 ?
This fault indicates that the 'Activate fault 1' function has been triggered via the NetWordIN1 data word. The activation signal was detected within the NetWordIN1 data word 0x4008:001 (P590.01). This fault type typically results in the motor being brought to a standstill.
Causas comunes
- The network master (e.g., PLC) is setting the 'Activate fault 1' bit within NetWordIN1 (Parameter 0x4008:001 (P590.01)) erroneously.
- Logical fault in the PLC or network master program, causing an incorrect value to be written to NetWordIN1.
- Communication issues on the industrial network, leading to corrupted or incorrect data in NetWordIN1.
- Parameter 0x4008:001 (P590.01) is mapped to a process value that has exceeded its configured threshold, triggering the fault.
- Malfunctioning network interface card or module on the drive, misinterpreting network data.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Use network diagnostic tools (e.g., Wireshark, PLC diagnostics) to monitor the exact value of NetWordIN1 (Parameter 0x4008:001 (P590.01)) from the master.
- 2
Examine the network master's program logic (e.g., PLC code) for the conditions that cause the 'Activate fault 1' bit in NetWordIN1 to be set.
- 3
Inspect the network cabling (e.g., Ethernet, Profibus) and connectors for physical damage or loose connections.
- 4
Verify the network communication parameters (e.g., IP address, baud rate, node ID) on both the drive and the network master.
- 5
Temporarily disable the 'Activate fault 1' function linkage to NetWordIN1 in the drive's configuration to confirm if the network signal is the source.