Traduciendo...
28833

Analog output 1 fault

Lenze · i550 Protec Drive

¿Qué significa 28833 ?

An open circuit or short circuit condition has been detected at analog output 1. This could prevent proper signal transmission to connected devices.

Causas comunes

  • Open circuit in the wiring between Analog Output 1 (e.g., 0-10V, 4-20mA) and the connected receiving device.
  • Short circuit in the wiring from Analog Output 1 to ground or to an adjacent signal line.
  • Faulty input impedance or internal short within the receiving device connected to Analog Output 1.
  • Overload condition on Analog Output 1 if it's attempting to drive a low-impedance load that exceeds its current capability.
  • Internal hardware failure of the Analog Output 1 circuit within the drive.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the load from Analog Output 1 terminals (e.g., X4.1, X4.2) and measure the output voltage or current with a multimeter.

  2. 2

    Measure the resistance of the wiring from Analog Output 1 to the receiving device to check for open (e.g., infinite ohms) or short circuits (e.g., near 0 ohms).

  3. 3

    Measure the input impedance of the receiving device connected to Analog Output 1 to ensure it is within the drive's specified load range.

  4. 4

    Reconnect the load and monitor the current draw from Analog Output 1 (if measurable) to confirm it does not exceed the drive's specifications.

  5. 5

    Temporarily connect a known, functional test load (e.g., 500 ohm resistor for 4-20mA, 10k ohm for 0-10V) to Analog Output 1 to test its integrity.

Ver todos los códigos en este manual (52)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas