E.OLT

Stall Prevention Trip

Mitsubishi Electric · FR-D700 Inverter

¿Qué significa E.OLT ?

This fault occurs when the inverter's output frequency drops to 1Hz due to stall prevention operation and remains at that level for 3 seconds, ultimately leading to an inverter trip. The display shows "OL" during active stall prevention. This indicates that the motor is experiencing a continuous overload condition that the stall prevention function cannot overcome. Sustained overload can lead to motor and inverter damage.

Causas comunes

  • Excessive mechanical load on the motor causing it to slow down significantly, leading to the inverter's stall prevention (current limit) to activate.
  • Incorrectly set stall prevention level (e.g., Pr. 156-Pr. 159 related parameters) causing it to trip too easily under normal load.
  • Motor's rated torque or power being insufficient for the application, leading to continuous overload conditions.
  • Mechanical binding or jamming in the driven machinery, impeding motor rotation and increasing torque demand.
  • Parameter Pr. 155 (Stall prevention operating frequency) is set too high, triggering the trip condition prematurely.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the actual motor operating current and speed under load and compare to the motor's rated specifications.

  2. 2

    Inspect the mechanical system (gears, bearings, belts, shafts) for binding, excessive friction, or physical damage.

  3. 3

    Review and adjust stall prevention parameters (e.g., Pr. 156, Pr. 157, Pr. 158) to ensure they are appropriate for the motor and load characteristics.

  4. 4

    Increase the acceleration time (Pr. 7) to allow the motor more time to overcome inertia without stalling during startup.

  5. 5

    Verify the motor parameter settings (Pr. 9, Pr. 71, Pr. 80, Pr. 81) match the actual motor nameplate data.