Inverter Reset
Mitsubishi Electric · FR-D700 Inverter
¿Qué significa Inverter reset ?
The reset signal (RES signal) is ON, causing the inverter to immediately shut off its output. This indicates that a reset command has been issued, either manually through a control signal or automatically by the system, placing the inverter in a non-operational state.
Causas comunes
- The external reset input (RES terminal) is continuously activated due to a wiring fault (e.g., short to common) or a stuck external relay contact.
- An external control system (e.g., PLC) is erroneously sending a continuous ON signal to the inverter's RES terminal.
- The inverter's internal reset button (if present) is stuck in the ON position or has been pressed accidentally.
- A temporary power glitch causing the reset circuit to activate.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the wiring to the RES terminal on the inverter's control terminal block for any shorts or damage.
- 2
Verify the status of the external reset command source (e.g., PLC output, physical button) using a multimeter to confirm it is OFF.
- 3
Temporarily disconnect the wire from the RES terminal and observe if the inverter powers on without the reset error.
- 4
Check the inverter's event log for recurring faults that might automatically trigger a reset (e.g., overcurrent, overvoltage).
- 5
Cycle power to the inverter and then re-enable the external reset signal, if applicable, to test its functionality.