A0 H
Output short-circuit detection
Mitsubishi Electric · MELSEC iQ-R I/O Module
¿Qué significa A0 H ?
A short-circuit has been detected on an output terminal. This indicates an abnormally low resistance path, likely causing excessive current flow, which can damage the module or connected components if not addressed promptly.
Causas comunes
- Short-circuit in the output wiring between the module and the load.
- Internal short-circuit within the connected output load (e.g., actuator, solenoid).
- Damage to the output terminal itself, creating a short.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Identify and eliminate the short-circuit in the output wiring or connected load.
- 2
After recovery from the short-circuit, turn 'Alarm clear request' (Y11) on and off to clear the alarm.
- 3
Verify that 'Output short-circuit detection status' reads 0 (Normal) and 'Alarm flag' (X11) turns off after clearing.
Datos técnicos verificados. Última actualización: March 2026