AC Input Signal Not Turning ON

Mitsubishi Electric · MELSEC iQ-R I/O Module

¿Qué significa AC-INPUT-NO-ON ?

An AC input signal fails to turn on, typically caused by step-like deformations in the input signal waveform around the zero-cross voltage. This issue often arises from power supply quality problems, such as those associated with off-line type Uninterruptible Power Supplies (UPSs).

Causas comunes

  • Deformed input signal waveform around the zero-cross voltage, preventing proper detection by the AC input module.
  • Use of an off-line type UPS or other power supply that generates insufficient or distorted AC waveforms.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Improve the input signal waveform by using an on-line type UPS or other power conditioning device that provides a cleaner, stable AC waveform.