Traduciendo...
F107
Baton Pass Error (Baton Lost)
Mitsubishi Electric · MELSEC Q-series MELSECNET/H
¿Qué significa F107 ?
The network's baton pass mechanism has failed, resulting in a lost baton. This prevents proper communication and data exchange across the network.
Causas comunes
- Faulty network cable
- Uninstalled terminating resistor on the network line
- One or more network stations are not powered on
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Inspect the entire network line for any faulty cables or physical damage
- 2
Verify the correct installation and integrity of all terminating resistors on the network bus
- 3
Confirm that all stations connected to the network are properly powered on
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Mitsubishi Electric MELSEC Q-series MELSECNET/H