1005

CPU Down Error

Mitsubishi Electric · MELSEC System Q/L Series

¿Qué significa 1005 ?

The CPU module has experienced a runaway condition or failure, potentially due to electrical noise or a hardware fault. For Qn(H), QnPH, and QnPRH models, this error can also occur if a boot operation was performed without formatting the program memory.

Causas comunes

  • Runaway or failure of CPU module.
  • Malfunctioning due to noise or other external reasons.
  • Hardware fault within the CPU module.
  • Boot operation was performed in the transfer destination without formatting program memory (Qn(H), QnPH, QnPRH models).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Implement noise reduction measures for the control system environment.

  2. 2

    Reset the CPU module and attempt to RUN it again.

  3. 3

    If the same error is displayed again after resetting, diagnose for a CPU module hardware fault.

  4. 4

    Before performing boot operation by the parameter, select 'Clear program memory' to clear the program memory.

Ver todos los códigos en este manual (53)