1106
RAM ERROR
Mitsubishi Electric · MELSEC System Q/L Series
¿Qué significa 1106 ?
The program memory in the CPU module is faulty. This error is detected during a STOP to RUN transition or when an END instruction is executed, indicating an issue with the stored program logic.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the battery to see if it is dead or not. If dead, replace the battery.
- 2
Take noise reduction measures.
- 3
Format the program memory, write all files to the PLC, then reset the CPU module and RUN it again. If the same error is displayed again, this suggests a CPU module hardware fault.