Traduciendo...
E6

Indoor/Outdoor Communication Miswiring/Disconnection

Mitsubishi Electric · PAR-21MAA MA Remote Controller

¿Qué significa E6 ?

This error indicates a communication problem between indoor and outdoor units, specifically due to incorrect wiring (converse wiring) or a complete disconnection of the communication wire. This prevents the units from exchanging essential control signals, causing system failure.

Causas comunes

  • Communication wiring between indoor and outdoor units is loose, disconnected, or broken.
  • Faulty communication interface board on either the indoor or outdoor unit.
  • Excessive noise or interference on the communication line.
  • Incorrect wiring gauge or length exceeding specifications.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the indoor/outdoor connecting wire terminations match the wiring diagram for correct connection, checking for converse wiring or disconnections.

  2. 2

    Inspect the indoor/outdoor connecting wire and power supply for signs of electrical noise interference that could disrupt communication.

  3. 3

    Cycle power to the unit (turn off, then on again) to re-check for the error.

Ver todos los códigos en este manual (26)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric PAR-21MAA MA Remote Controller