F1

Outdoor Terminal Block Incorrect Connection

Mitsubishi Electric · PAR-21MAA MA Remote Controller

¿Qué significa F1 ?

The outdoor unit's power supply terminals (L1, L2, L3) or communication terminals (S1, S2, S3) have incorrect connections. This prevents the remote controller from operating and keeps displaying 'PLEASE WAIT'. The outdoor board LED will blink green once and red once alternately after system startup.

Causas comunes

  • Incorrect wiring connections to the outdoor unit's terminal block.
  • Wires not properly secured in the terminal block.
  • Wrong wire gauge used for terminal connections.
  • Loose or corroded terminal connections.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the wiring of L1, L2, L3 power supply terminals at the outdoor unit according to the system's wiring diagram.

  2. 2

    Verify the wiring of S1, S2, S3 communication terminals between the indoor and outdoor unit for correct polarity and secure connection.

  3. 3

    Measure insulation resistance between the ground and the power supply terminal block (L, N) on the outdoor unit using a 500V Megger; expect a reading of 1.0 MΩ or over.

Ver todos los códigos en este manual (26)
Datos técnicos verificados. Última actualización: March 2026