E8 (6810)

Indoor/Outdoor Unit Communication Error (Outdoor Receiving)

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

¿Qué significa E8 (6810) ?

The outdoor controller circuit board fails to receive any signal normally for 10 minutes. This can be caused by contact failure in the indoor/outdoor unit connecting wire, defective communication circuits in either the outdoor controller board or the indoor controller board, or noise interference within the indoor/outdoor unit connecting wire.

Causas comunes

  • Outdoor unit fails to receive communication signals from indoor unit.
  • Damaged or disconnected communication wiring.
  • Faulty indoor unit control board.
  • Interference on the communication line.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check for disconnection or looseness of the indoor/outdoor unit connecting wire at both the indoor and outdoor units.

  2. 2

    Turn the power off, then on again. If the abnormality reappears, replace the indoor controller board or outdoor controller circuit board.