Traduciendo...
Ed (00)

Serial communication error

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

¿Qué significa Ed (00) ?

This error indicates a failure in serial communication. It can occur between the outdoor controller circuit board and the outdoor power circuit board, or between the outdoor controller circuit board and the M-NET board. Causes include broken wires, contact failures in connectors (CN, CNMNT, CND), defective communication circuits on the boards, or noise interference on the M-NET transmission wire.

Causas comunes

  • Serial communication failure between main control board and peripheral devices.
  • Incorrect serial communication protocol setting (e.g., Baud rate, parity).
  • Damaged communication wiring.
  • Faulty communication interface on one of the devices.
  • Interference on communication lines.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the connection of connectors CN and CN between the outdoor controller circuit board and the outdoor power circuit board for disconnections or contact failures.

  2. 2

    Check the connection wire between the outdoor controller circuit board (CNMNT) and the M-NET board (CN and CND) for disconnection, looseness, or breaking.

  3. 3

    Review the M-NET transmission wiring method for proper installation.

  4. 4

    If communication between the outdoor controller and outdoor power board fails, replace the outdoor power circuit board.

  5. 5

    If communication between the outdoor controller and outdoor power board fails, replace the outdoor controller circuit board.

Ver todos los códigos en este manual (45)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Mitsubishi Electric PUZ-HA30/36NHA4 Outdoor Unit