EF (6607 or 6608)

Non-Defined Error Code

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

¿Qué significa EF (6607 or 6608) ?

This code is displayed when the unit receives an undefined error code. Possible root causes include noise in the remote controller transmission wire or indoor/outdoor connecting wire, the outdoor unit not being an inverter model, or the use of an incompatible remote controller model (PAR-S21A).

Causas comunes

  • Unspecified error code detected by the system.
  • Potential software anomaly or unknown operational state.
  • Requires further diagnosis based on system logs.
  • Check for other active error codes.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Turn the power off, then on again. If the abnormality reappears, replace the indoor controller board or outdoor controller circuit board.

  2. 2

    If the outdoor unit is not an inverter model, replace it with an inverter model.

  3. 3

    If the remote controller model is PAR-S21A, replace it with an MA remote controller.