Open/Short of Outdoor Unit Thermistors

Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit

¿Qué significa U3 ?

An open or short circuit is detected in one or more outdoor unit thermistors (TH3, TH32, TH33, TH6, TH7, and TH8). These sensors are critical for monitoring various temperatures within the outdoor unit's refrigerant circuit and ambient conditions, affecting system control. Open detection for TH3, TH32, TH33, TH6 is inoperative for 10 seconds to 10 minutes after compressor start and 10 minutes after/during defrosting.

Causas comunes

  • Open circuit or short circuit detected in the outdoor unit's thermistor sensors.
  • Damaged or disconnected thermistor wiring.
  • Faulty thermistor (e.g., ambient, coil).
  • Corrosion on sensor terminals.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the connection of connectors (TH3, TH32, TH33, TH7/6) on the outdoor controller circuit board.

  2. 2

    Check the connection of connector (CNAF) on the outdoor power circuit board.

  3. 3

    Check the lead wires for thermistors (TH3, TH32, TH33, TH6, TH7, TH8) for any breaks or damage.

  4. 4

    Measure the resistance value of each thermistor (TH3, TH32, TH33, TH6, TH7, TH8) and compare it to expected values for the measured temperature.

  5. 5

    If thermistors and wiring are confirmed correct, replace the outdoor controller circuit board.