Power Module Abnormality
Mitsubishi Electric · PUZ-HA30/36NHA4 Outdoor Unit
¿Qué significa U6 ?
An abnormality is detected in the power module, often signaled by overcurrent during module operation (which can trigger UF or UP errors). This critical fault can be caused by a closed outdoor stop valve, low power supply voltage, incorrect or loose compressor wiring, or a defective compressor or outdoor power circuit board.
Causas comunes
- Power module failure or internal short circuit.
- DC bus voltage abnormal.
- Control board communication error with power module.
- Overcurrent or overvoltage protection triggered within the power module.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify that the outdoor stop valve is fully open.
- 2
Check the facility's power supply voltage to ensure it meets the system specifications.
- 3
Correct the wiring (U, V, W phase) to the compressor if any connections are loose, disconnected, or conversed.
- 4
Check the compressor for defects, referring to diagnostic procedures in section 10-6 of the manual.
- 5
If the above steps do not resolve the issue, replace the outdoor power circuit board.